Yokogawa ADV569 Digital Output Module

Yokogawa ADV569 Digital Output Module

Views:83

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
Parameter
FAQ
Products Description
https://www.tilgames.com/wp-content/uploads/2025/03/ADV569-1.jpg
https://www.tilgames.com/wp-content/uploads/2025/03/ADV569-4.jpg
https://www.tilgames.com/wp-content/uploads/2025/03/ADV569-2.jpg
https://www.tilgames.com/wp-content/uploads/2025/03/ADV569-3.jpg
Company Information
E-mail sales@xmjzjsgs.com
Mobile +8613666033393
Whatsapp +8613666033393
WeChat 13666033393
Parameter

Manufacturer:Yokogawa

Product Number:ADV569

Product Type:Digital Output Module

Origin:Japan

Dimensions:130 x 127.2 x 32.8 mm

Weight:0.3 kg

FAQ

Frequently Asked Questions (FAQ)

Q1: What type of outputs does the ADV569 module support?
A1: The ADV569 supports transistor contact outputs with three modes: Status Output (SO), Pulse Width (PW), and Time-Proportioning (TP).

Q2: Can I mix PW and TP outputs on the same module?
A2: Yes, but they must follow specific terminal pairing rules. Contiguous terminal pairs must be assigned to the same function (PW or TP).

Q3: Is the ADV569 suitable for use in dual-redundant systems?
A3: No, ADV569 is designed for direct-connected node configurations. Dual redundancy is not supported for this model.

Q4: What kind of load can be driven by the ADV569 output?
A4: The outputs can drive inductive or resistive loads up to 100 mA per channel at 30 V DC. A diode is recommended when driving DC relays.

Q5: How is electrical isolation handled in the ADV569?
A5: Channels are isolated in groups of 16, and withstand voltages are 2 kV AC (signal to system) and 500 V AC (between commons).

Q6: What is the response time of the ADV569 outputs?
A6: The module achieves an output response time of up to 16 ms, ensuring real-time control performance.

Q7: What connector is required for field connection?
A7: The ADV569 uses a dedicated KS9 cable for external connection.

Q8: What are the environmental conditions supported by this module?
A8: The standard model supports temperatures from 0°C to 55°C. Models with suffix -3 are suitable for extended environments up to 70°C.