Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 | |||
Add | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China |
Technical Specifications
Parameter | Value |
---|---|
Range of Product | Modicon Quantum Automation Platform |
Product Type | DIO Drop Interface |
Number of Ports | 1 (Single) |
Rated Supply Voltage [Us] | 115/230 V AC |
Supply Voltage Limits | 85…276 V |
Supply Frequency | 47…63 Hz |
Max. Supply Current | 0.2 A (115 V) / 0.4 A (230 V) |
Inrush Current | 10 A (115 V) / 20 A (230 V) |
Rated Power Consumption | 50 VA |
Associated Fuse Rating | 1.5 A |
Output Voltage | 5.1 V |
Nominal Output Current | 3 A |
Minimum Load Current | 0 A |
Short-Circuit Protection | Provided |
Overvoltage Protection | Provided |
I/O Word Allocation | 30 Inputs / 32 Outputs |
Compatible Backplane Sizes | 2, 3, 4, 6, 10, 16 positions |
Diagnostics at Startup | RAM Address, RAM, Checksum |
Diagnostics during Operation | RAM Address, RAM, Checksum |
Power Dissipation | 11 W |
Terminal Connections | 7-pole Terminal Block |
Module Format | Standard |
Electrostatic Discharge | 4 kV Contact / 8 kV Air (IEC 801-2) |
EM Field Resistance | 9.1 V/m (10 V/m) 80–2000 MHz (IEC 801-3) |
Operating Temperature | 32 to 140 °F (0 to 60 °C) |
Storage Temperature | -40 to 185 °F (-40 to 85 °C) |
Relative Humidity | 95% non-condensing |
Maximum Operating Altitude | 5000 m (16404.2 ft) |
Protective Treatment | TC |
Standards | UL 508 |
Certifications | UL, CSA Class 1 Div. 2, DNV, C-tick, GOST |
Package Dimensions (mm) | 50 × 165 × 315 |
Package Weight | 0.689 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What is the function of the 140CRA21110 module?
A1: It acts as a DIO (Digital Input/Output) drop interface for connecting remote I/O to a Modicon Quantum automation platform.
Q2: How many I/O words does the module support?
A2: It supports 30 input words and 32 output words.
Q3: What is the output voltage and current capacity?
A3: The module outputs 5.1 V with a nominal output current of 3 A.
Q4: What types of diagnostic checks are supported?
A4: It provides RAM address, RAM content, and checksum diagnostics at startup and runtime.
Q5: Is short-circuit and overvoltage protection available?
A5: Yes, the module includes both protections.
Q6: What backplane configurations are supported?
A6: The module supports 2, 3, 4, 6, 10, and 16-position backplanes.
Q7: What are the installation environment limits?
A7: Operating temperature ranges from 0 to 60°C, with up to 95% humidity (non-condensing) and altitudes up to 5000 m.
Q8: Which certifications does the 140CRA21110 carry?
A8: It is certified by UL, CSA (Class 1 Div. 2), DNV, C-tick, and GOST.