Parameter | Details |
---|---|
Module Model | CC-PAOH51 |
Function | Analog Output Module with HART support |
Output Channels | 16 channels |
Output Type | 4–20 mA current output |
Output Ripple | < 100 mV peak-to-peak across 250 Ω load |
Temperature Drift | 0.005% of Full Scale per °C |
Output Readback Accuracy | ±4% of Full Scale |
Output Current Linearity | ±0.05% of Full Scale |
Resolution | ±0.05% of Full Scale |
Calibrated Accuracy | ±0.35% of Full Scale (at 25°C incl. linearity) |
Direct Output Current Range | 0 mA, 2.9 mA to 21.1 mA |
Max Resistive Load | 800 ohms (at 24 V supply) |
Max Compliance Voltage | 16 V |
Max Open Circuit Voltage | 22 V |
Response Time | Within 80 ms to reach within ±1% of final value |
Redundancy Switchover Gap | 10 ms max (redundant mode only) |
FAILOPT Output Behavior | Configurable per channel: hold last or safe value |
Open Wire Detection | Supported with channel soft failure indication |
Dimensions (mm) | 63.5 x 124.46 x 307.34 |
Weight | 0.299 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: How many output channels does the CC-PAOH51 module support?
A1: The module supports 16 analog output channels (4–20 mA).
Q2: Does it support HART communication?
A2: Yes, it supports HART for device configuration and status monitoring.
Q3: Is redundancy supported for this module?
A3: Yes, redundancy is supported via compatible IOTA base units.
Q4: What is the maximum resistive load it can drive?
A4: It can drive up to 800 ohms with a 24V power supply.
Q5: Is open wire detection available?
A5: Yes, the module can detect open field wiring and flag a soft fault.
Q6: What happens to output during a failure?
A6: Each channel can be configured to either hold the last value or go to a safe value.
Q7: What is the response time of the output?
A7: The output settles to within 1% of the final value in 80 ms.
Q8: Is an external power supply needed?
A8: No, the module is powered through the connected IOTA.