Technical Specifications
Parameter | Description |
---|---|
Module Type | Universal Analog Input Slave Module |
Channels | 16 individually configurable analog input channels |
Input Signal Types | Thermocouple (E, J, K, L, N, R, S, T, U, Chinese E/S), Millivolt, RTD, Voltage, Current |
A/D Conversion Resolution | Programmable from 16 to 24 bits |
Voltage Input Range | -10 V to +10 V (high level), -100 mV to +100 mV (low level) |
Current Input | 4-20 mA (internal or external powered) |
RTD Types | 3-wire: 10Ω Cu, 100Ω Pt (US/Euro), 120Ω Ni, Chinese 53Ω |
Cold Junction Compensation | ±0.5°C accuracy |
Temperature Linearization | ±0.1°C accuracy (software linearization) |
Lead Wire Resistance Compensation | Supported (configurable) |
Conversion Time per Channel | 16-bit: 30ms, 24-bit: 2000ms |
Normal Mode Rejection | ≥ 80 dB at 50/60 Hz |
Common Mode Isolation | 250 VRMS channel-to-channel and channel-to-ground |
Input Impedance | ≥ 10 MΩ |
Input Setting Time | ≤ 0.5 seconds to 1% of full scale |
Operating Temperature Range | 0°C to 70°C (32°F to 158°F) |
Relative Humidity | 5% to 95% (non-condensing) |
Power Consumption | +5 VDC: typ. 300 mA, max. 450 mA; +15 VDC: typ. 130 mA, -15 VDC: typ. 35 mA |
Mounting | Occupies one slot in standard INFI 90 MMU |
Dimensions | 279.4 x 355.6 x 55.4 mm |
Weight | 1.146 kg |
Certifications | CSA certified, IEEE-472 surge tested |
FAQ
FAQ
Q1: How many analog inputs does the IMASI03 module support?
A1: It supports 16 independently configurable analog input channels.
Q2: Can the IMASI03 module accept mixed signal types?
A2: Yes, each channel can be individually set for thermocouple, RTD, voltage, millivolt, or current inputs.
Q3: What resolution is available for analog-to-digital conversion?
A3: The resolution is selectable from 16 to 24 bits per channel.
Q4: Is cold junction compensation available for thermocouple inputs?
A4: Yes, either built-in or remote cold junction compensation is supported.
Q5: What is the module’s method of input isolation?
A5: Each channel has an isolation amplifier providing 250 VRMS isolation.
Q6: How is lead wire resistance handled?
A6: The module compensates for lead wire resistance via configurable parameters.
Q7: Can the module be hot-swapped?
A7: Yes, it can be installed or removed without powering down the system.
Q8: How is calibration handled for input accuracy?
A8: Factory calibration is stored in NVRAM; automatic recalibration compensates for drift during operation.