Technical Specifications
Parameter Category | Specification |
---|---|
Module Model | DC-TAIL51 |
Compatible Module | CC-PAIL51 (Low-Level Analog Input – Temperature) |
Input Type | Thermocouple (TC), RTD |
Number of Channels | 16 channels, fully isolated (channel-to-channel, channel-to-DCS, channel-to-power) |
Input Scan Rate | Fixed 1 second |
Channel Bandwidth | 0–4.7 Hz (-3 dB) |
TC Nominal Input Range | -20 to +100 mV |
TC Max Input (no damage) | -10 to +10 V |
RTD Max Input | -1 to +2 V @ 100 mA |
Gain Error | Max ±0.05% full-scale |
Temperature Stability | ±20 ppm/°C (TC and RTD) |
Long-Term Drift | 500 ppm max |
Input Impedance (TC) | 1 MΩ at DC |
Common Mode Voltage | ±250 VAC/DC RMS |
Channel-to-Channel Voltage | ±33 VAC/DC RMS |
Channel-to-Shield Voltage | ±250 VAC/DC RMS |
Crosstalk | ≥80 dB (120 dB at 50/60 Hz) |
Normal Mode Rejection | ≥60 dB (50/60 Hz) |
Line Frequency Integration | 50 Hz or 60 Hz fixed |
RTD Excitation Current | 1 mA |
Cold Junction Compensation | -20 to +60°C (±0.5°C typical) |
TC Linearization Accuracy | ±0.05 Ω/°C |
Open Thermocouple Detect | ≤1000 Ω = no trip, ≥1500 Ω = trip |
RTD Lead Wire Resistance | Max 15 Ω |
Surge Protection | EN 61000-4-5 compliant (sensor and serial/power interface) |
Dimensions | 95 × 135 × 25 mm |
Weight | 0.3 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What sensor types are supported by DC-TAIL51?
A1: It supports both thermocouple (TC) and RTD sensors, including platinum, nickel, and copper types.
Q2: Are the channels electrically isolated?
A2: Yes, all channels are isolated from each other, from power, and from the control system.
Q3: Is cold junction compensation included?
A3: Yes, built-in cold junction compensation covers -20°C to +60°C, with typical accuracy of ±0.5°C.
Q4: Does it support open thermocouple detection?
A4: Yes, each channel includes OTD detection to prevent erroneous control signals.
Q5: How is channel crosstalk handled?
A5: The module features excellent crosstalk rejection—80 dB generally and up to 120 dB at line frequency.
Q6: What is the scan rate per input point?
A6: The scan rate is fixed at 1 second per input channel.
Q7: Is surge protection available?
A7: Yes, surge protection per EN 61000-4-5 is integrated for both sensor and interface terminals.
Q8: What thermocouple types are supported?
A8: It supports ANSI-standard types B, E, J, K, R, S, T for a wide industrial temperature range.