Parameter | Description |
---|---|
Product Range | Modicon Quantum Automation Platform |
Product Type | DC Discrete Output Module |
Number of Discrete Outputs | 32 |
Grouping | 4 groups of 8 |
Output Logic | Negative logic (sink) |
Addressing Requirement | 2 output words |
Rated Output Voltage | 24 V DC |
Output Voltage Limits | 19.2 to 30 V DC |
Absolute Max Output | 50 V for 1 s (decaying pulse) |
Max Voltage Drop | < 0.4 V at 0.5 A |
Max Load Current | 16 A per module, 4 A per group |
Surge Current | 5 A for 1 ms |
Response Time | ≤ 1 ms (0 ↔ 1 or 1 ↔ 0) |
Max Leakage Current | 0.4 mA at 30 V |
Load Inductance | L(H) = 0.5 / [(I(A))² × (Switch Freq(Hz))] |
Max Tungsten Load | 12 W at 24 V |
Fault Indication | Loss of field power, blown fuse |
Fuse Rating | 3 A per point, 5 A per group |
Isolation: Channel ↔ Bus | 1780 Vrms DC for 1 min |
Isolation: Group ↔ Group | 500 Vrms DC for 1 min |
Protection Type | Internal 5 A fuse per group |
Power Dissipation | 2.0 W + (0.4 V × total load current) |
Local Signalling | 1 green LED (bus active), 1 red LED (fault), 32 green LEDs (status) |
Bus Current Requirement | 330 mA |
Module Format | Standard |
Dimensions | 103.9 × 40.3 × 250 mm |
Net Weight | 0.45 kg (0.99 lb) |
Certifications | CE, FM Class 1 Div 2, RINA, GOST, C-tick, RMRS |
Standards | UL 508, CSA C22.2 No 142 |
ESD Resistance | 4 kV (contact), 8 kV (air) IEC 801-2 |
EMC Resistance | 9.1 V/m (10 V/m) 80–2000 MHz IEC 801-3 |
Operating Temperature | 0 to 60 °C (32 to 140 °F) |
Storage Temperature | -40 to 85 °C (-40 to 185 °F) |
Relative Humidity | 95% non-condensing |
Operating Altitude | ≤ 5000 m (16404.2 ft) |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of logic does the 140DDO35310 output module use?
A1: It uses negative logic (sink type) for output control.
Q2: How many discrete outputs are available on this module?
A2: The module offers 32 discrete outputs, organized in 4 groups of 8.
Q3: What is the maximum load current the module can support?
A3: It supports up to 16 A per module and 4 A per group.
Q4: What kind of protection is integrated into the module?
A4: Each group is protected with an internal 5 A fuse.
Q5: How does the module signal a blown fuse or field power loss?
A5: It provides LED indicators for external faults and power loss.
Q6: What is the response time for output transitions?
A6: The response time is less than or equal to 1 ms for both ON and OFF transitions.
Q7: What is the size and weight of this module?
A7: The dimensions are 103.9 × 40.3 × 250 mm, and it weighs 0.45 kg.
Q8: Is this module certified for use in hazardous environments?
A8: Yes, it is certified under FM Class 1 Division 2, among others.