Technical Specifications
Parameter Category | Specification |
---|---|
Product Range | Modicon Quantum Automation Platform |
Product Type | Relay Discrete Output Module |
Number of Outputs | 16 |
Contact Type and Makeup | 1 Normally Open (1 NO) |
Contact Form | Form A |
Output Voltage Range | 20…250 V AC 30…150 V DC 5…30 V DC |
Addressing Requirement | 1 output word |
Minimum Load | 50 mA @ 20…250 V AC 50 mA @ 5…30 V DC |
Maximum Load Current | 1 A @ 250/30 V AC/DC (inductive load, cos φ = 0.4) 1 A tungsten 2 A resistive @ 250/30 V AC/DC @ 60°C 300 mA @ 30…50 V DC resistive |
Surge Current | 10 A for 10 ms (capacitive load) |
Switching Capacity | 500 VA (resistive load) |
Max Response Time | 10 ms (state 0 to 1) 20 ms (state 1 to 0) |
Mechanical Durability | 10 million cycles |
Electrical Durability | 100,000 cycles @ 100 mA, 30…150 V DC (L/R = 10 ms) 100,000 cycles @ 2 A, 30 V DC resistive 100,000 cycles @ 30…150 V DC relay 100,000 cycles @ 300 mA, 30…150 V DC resistive 200,000 cycles @ 2 A, 250 V AC resistive 50,000 cycles @ 500 mA, 30…150 V DC resistive |
Overvoltage Protection | Internal varistor, 275 V |
Channel Isolation | 1780 Vrms AC for 1 minute |
Bus Isolation | 1780 Vrms AC / 2500 V DC for 1 minute |
Power Dissipation | 5.5 W + (0.5 W × number of active points) |
Communication Indicator | 1 green LED (active) |
Fault Indicator | 1 red LED (fault) |
Status Indicators | 16 green LEDs (1 per channel) |
Bus Current Requirement | 1100 mA |
Module Dimensions (L×W×H) | 103.9 × 40.3 × 250 mm |
Net Weight | 0.41 kg (0.90 lb) |
Module Format | Standard |
Certifications | CE, FM Class 1 Div 2, C-tick, GOST, ABS |
Standards Compliance | UL 508, CSA C22.2 No 142 |
ESD Resistance | 4 kV contact, 8 kV air (IEC 801-2) |
EMI Resistance | 9.1 V/m (80–2000 MHz, IEC 801-3) |
Operating Temperature | 0…60°C (32…140°F) |
Storage Temperature | -40…85°C (-40…185°F) |
Relative Humidity | 95% non-condensing |
Operating Altitude | ≤5000 m (16404.2 ft) |
FAQ
Frequently Asked Questions (FAQ)
Q1: What types of loads does the 140DRA84000 support?
A1: It supports resistive, inductive (cosφ = 0.4), and tungsten loads, up to 2 A.
Q2: How many output channels are available in this module?
A2: The module provides 16 independent relay output channels.
Q3: What is the maximum surge current per channel?
A3: Each channel supports up to 10 A for 10 milliseconds with capacitive loads.
Q4: What is the minimum load requirement?
A4: Minimum load is 50 mA, applicable across AC (20–250 V) and DC (5–30 V).
Q5: Is electrical isolation provided between channels?
A5: Yes, isolation between channels is 1780 Vrms AC for 1 minute.
Q6: What is the electrical life of the module?
A6: Depending on the load type, it ranges from 50,000 to 200,000 cycles.
Q7: Does the module include overvoltage protection?
A7: Yes, it has built-in 275 V varistor protection.
Q8: What are the environmental requirements for installation?
A8: Operating temperature is 0–60°C, storage -40–85°C, and max altitude 5000 meters.