Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 |
Technical Specifications
Parameter | Specification |
---|---|
Analog Input Channels | 15 independently configured channels |
Input Signal Ranges | 4–20 mA, 1–5 VDC, 0–1 VDC, 0–5 VDC, 0–10 VDC, ±10 VDC |
A/D Conversion Rate | 5 conversions per second |
A/D Resolution | 14 bits with polarity |
Accuracy | ±0.1% (±0.25% for 0–1 VDC range) |
Common Mode Voltage Range | -12 VDC to +15 VDC |
Common Mode Rejection | ≥90 dB @ 50/60 Hz |
Normal Mode Rejection | ≥70 dB @ 50/60 Hz |
Input Impedance | >1 MΩ per channel |
Power Requirements | +5 VDC @ 85 mA, +15 VDC @ 25 mA, -15 VDC @ 20 mA |
Power Consumption | 1.1 W typical |
Communication Baud Rate | 9600 Baud |
Operating Temperature | 0°C to 55°C (non-condensing) |
Relative Humidity | 5% to 95% (up to 55°C); 5% to 45% (at 70°C) |
Atmospheric Pressure | Sea level to 3 km |
EMC Compliance | EN50081-2, EN50082-2, EN61010-1 |
Mounting | Occupies one slot in INFI 90 OPEN module rack |
Dimensions | 229 x 103 x 33 mm |
Weight | 1 kg |
Certifications | CSA, FM (pending), Class I Div 2 & Class II Div 2 approved |
FAQ
Frequently Asked Questions
Q1: How many analog channels does the IMFEC12 support?
A1: It supports up to 15 independently configured analog input channels.
Q2: What input signal ranges are supported by the IMFEC12?
A2: Supported ranges include 4–20 mA, 1–5 VDC, 0–1 VDC, 0–5 VDC, 0–10 VDC, and ±10 VDC.
Q3: Does IMFEC12 support digital communication?
A3: No, IMFEC12 only supports analog signals. For digital communication, use IMFEC11.
Q4: How much space does the module occupy in the system?
A4: It occupies one slot in a standard INFI 90 OPEN module mounting unit.
Q5: Is IMFEC12 suitable for use in harsh environments?
A5: Yes. It operates from 0°C to 55°C with up to 95% relative humidity in non-condensing environments.
Q6: Does the module have strong interference immunity?
A6: Yes. It provides ≥90 dB common mode rejection and ≥70 dB normal mode rejection.
Q7: What is the measurement accuracy of IMFEC12?
A7: The input accuracy is ±0.1%, and ±0.25% for the 0–1 VDC range.
Q8: How is the module connected to field instruments?
A8: Via connection to NTAI05 or NIAI04 analog termination units, which connect to field devices.