Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 |
Technical Specifications
Parameter Category | Specification |
---|---|
Probe Model | 330106-05-30-05-02-CN |
Type | Reverse Mount 3300 XL 8 mm Proximity Probe |
Mounting Thread | M10 x 1 |
Probe Tip Diameter | 8 mm |
Case Material | AISI 303 or 304 Stainless Steel |
Probe Cable | 75Ω triaxial FEP insulated cable with ClickLoc connector |
Cable Type | Standard, non-armored |
Total Length | 0.5 meter (1.6 feet) |
Electrical Connector | Miniature coaxial ClickLoc type |
Min. Cable Bend Radius | 25.4 mm |
Recommended Torque | Max 22.6 N·m; recommended 7.5 N·m |
Linear Range | 0.25 mm to 2.3 mm (10 mils to 90 mils) |
Recommended Gap Voltage | -9 VDC (approx. 1.27 mm gap) |
Incremental Scale Factor (ISF) | 7.87 V/mm ±5% (5 m system); ±6.5% (9 m system) |
Total Length | 0.5 meter |
Weight | Approx. 0.162 kg |
Operating Temp Range | -52°C to +177°C (standard); up to +218°C at tip for high-temp version |
Storage Temp Range | -52°C to +177°C |
IP Rating | IP54 or better (with proper wiring installation) |
Safety Approvals | CSA, ATEX, IECEx (Option Code 05) |
FAQ
Frequently Asked Questions (FAQ)
Q1: Is this probe suitable for high-temperature applications?
A1: Yes. The high-temperature version supports up to +218°C at the tip and +260°C for the cable.
Q2: Are special tools required for installation?
A2: No tools are needed. The ClickLoc connector clicks into place by hand tightening.
Q3: What applications is the 330106-05-30-05-02-CN used for?
A3: It is primarily used for vibration and position measurements on fluid-film bearing machines.
Q4: Is it compatible with non-XL components?
A4: Yes, but performance will be limited to that of the non-XL components.
Q5: What is the recommended mounting torque?
A5: 7.5 N·m is recommended. Do not exceed 22.6 N·m.
Q6: Can the probe operate in humid environments?
A6: Yes. It tolerates 93% relative humidity for up to 56 days with less than 3% ASF deviation.
Q7: What is the minimum shaft diameter this probe supports?
A7: Minimum is 50.8 mm; 76.2 mm or more is recommended to minimize cross-talk.
Q8: Can I mix different probe and extension cable lengths?
A8: Yes, but the total probe + cable length must match the Proximitor Sensor system length.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.