Technical Specifications
Item | Specification |
---|---|
Model | ALE111-S00 |
Physical Layer Interface | IEEE802.3 10BASE-T |
Connection Type | Point-to-point |
Connector Type | RJ-45 |
Transmission Mode | Half-duplex |
Transmission Speed | 10 Mbps |
Transmission Medium | 100-ohm unshielded twisted pair |
Max Transmission Length | 100 meters per segment (between FCS and subsystems or HUB) |
Installation | Mounted on ANB10, ANB11, ANR10, AFF50, AFV10, AFV30, AFV40 |
Number of Ports | 1 port |
Media Access Control | CSMA/CD |
Supported Communication | FA-M3, Modbus, MELSEC, YFGW, DARWIN/DAQSTATION, PLC-5/SLC500 |
Current Consumption | 0.5 A |
Communication Definitions | 128 definitions per ALE111 |
I/O Data Capacity | 1000 words/ALE111, 8000 words max per FCS |
Dimensions | 130 × 125.5 × 32.8 mm |
Weight | 0.3 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What protocols does the ALE111-S00 support?
A1: It supports TCP/IP communication with FA-M3, Modbus, MELSEC, YFGW, DAQSTATION, and PLC-5/SLC500.
Q2: Can the ALE111 module be used in a redundant configuration?
A2: Yes. Two ALE111 modules can be installed in adjacent slots of the same node unit for redundancy.
Q3: Does ALE111 support multiple protocols simultaneously?
A3: No. Each module can only be configured with one communication function at a time.
Q4: What is the maximum number of subsystems that can be connected?
A4: Up to 30 subsystems per ALE111 (protocol dependent), or up to 128 devices for YFGW.
Q5: Are there restrictions on installation locations?
A5: Yes, installation must be on designated units such as AFV, ANB, or AFF50 series.
Q6: Can ALE111 communicate with Schneider Modicon Quantum devices?
A6: Yes. Modbus/TCP communication with devices like 140NOE77100 is supported.
Q7: Can the module read/write bit and word-level data from PLCs?
A7: Yes. It supports both bit (coil) and word (register) data operations depending on the protocol.
Q8: What is the cable length limitation?
A8: The maximum communication segment length is 100 meters.