Yokogawa SDV531-L23 Digital Output Module

Yokogawa SDV531-L23 Digital Output Module

Manufacturer:Yokogawa

Product Number:SDV531-L23

Product Type:Digital Output Module

Origin:Japan

Dimensions:130 x 124 x 32.8mm

Weight:0.28kg

Views:4

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
https://www.tilgames.com/wp-content/uploads/2025/05/SDV531-L23-1-1.jpg
https://www.tilgames.com/wp-content/uploads/2025/05/SDV531-L23-3.jpg
https://www.tilgames.com/wp-content/uploads/2025/05/SDV531-L23-4.jpg
https://www.tilgames.com/wp-content/uploads/2025/05/SDV531-L23-5.jpg
Company Information
E-mail [email protected]
Mobile +8613666033393
Whatsapp +8613666033393
WeChat 13666033393

Technical Specifications

Item Specification
Model SDV531-L23
Number of Outputs 8 channels, module isolation
Output Voltage 24 V DC
Voltage Drop 1 V max
External Power Rating 24 V DC, minimum 5 A
External Power Supply 24 V DC +20% / –10%
Max Leakage Current (OFF) 1.6 mA
Output Type Current source
Max Load Current 0.6 A per channel, total ≤ 4.8 A
Min Load Current 35 mA
Load Resistance Range 40 to 685 Ω
Output Response Time 30 ms max
Withstand Voltage 2 kV AC between outputs and system for 1 minute
Current Consumption (5V) Max 280 mA
Current Consumption (24V) Max 140 mA
External Connections Pressure clamp terminal, MIL cable, AKB331/AKB651
Dimensions (W x H x D) 130 x 124 x 32.8 mm
Weight 0.28 kg
FAQ

Frequently Asked Questions (FAQ)

Q1: How many output channels does the SDV531-L23 support?
A1: It supports 8 isolated output channels.

Q2: What is the maximum load current per channel?
A2: Maximum 0.6 A per channel, with a total of 4.8 A across all channels.

Q3: What is the output voltage?
A3: 24 V DC with a maximum voltage drop of 1 V.

Q4: Does the module provide channel isolation?
A4: Yes, it provides module-level isolation per output.

Q5: What are the external power supply requirements?
A5: Requires 24 V DC with at least 5 A capacity, and voltage range of +20% / –10%.

Q6: What is the output response time?
A6: Maximum response time is 30 milliseconds.

Q7: What is the withstand voltage of this module?
A7: 2 kV AC between output signal lines and system for one minute.

Q8: What are the connection methods supported?
A8: It supports pressure clamp terminal, MIL cable, and dedicated signal cables such as AKB331 and AKB651.