Parameter
Manufacturer:Yokogawa
Product Number:AMN31-S1
Product Type:Nest for Terminal I/O Module
Origin:Japan
Dimensions:125 x 130 x 248 mm
Weight:2kg
FAQ
Frequently Asked Questions (FAQ)
Q1: How many modules can be installed in the AMN31-S1?
A1: Up to two digital I/O modules such as ADM11T or ADM51T can be installed.
Q2: Does the AMN31-S1 support analog I/O modules?
A2: No. The AMN31-S1 is designed specifically for digital I/O modules.
Q3: Where can the AMN31-S1 be installed?
A3: It can be installed in a Node Interface Unit or an I/O Expansion Rack.
Q4: What should I do if some slots are not used?
A4: Install dummy covers (model T9081CV) on unused slots to protect the backplane connectors.
Q5: How is power supplied to the AMN31-S1?
A5: 5.0 V DC is supplied from the Node Interface Unit.
Q6: Can the AMN31-S1 be mounted in a standard 19″ rack?
A6: Yes, but it requires the use of an I/O Expansion Rack.
Q7: Are signals isolated from the system?
A7: Yes, installed modules are isolated with a dielectric strength of 1500 V AC/min.
Q8: What precautions should be taken during installation?
A8: Avoid mixing incompatible modules like multiplexers with digital I/O modules, and ensure no heat source is placed below thermocouple modules.