Products Description




Company Information | |||
sales@xmjzjsgs.com | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 |
Technical Specifications
Parameter | Specification |
---|---|
Product Model | TU515 |
Ordering Code | 1SAP212200R0001 |
Operating Voltage | 24 V DC |
Max Allowed Current | 10 A per separated process voltage terminal |
Number of Channels | Up to 32 (4 groups × 8 channels) |
Grounding | Direct grounding via DIN rail or wall screws |
Terminal Type | Screw terminals, vertical connection to PCB |
Mounting Position | Horizontal or vertical |
Operating Temperature | 0°C to +60°C (horizontal), 0°C to +40°C (vertical, 50% load) |
Storage Temperature | -40°C to +70°C |
Humidity | Max. 95%, non-condensing |
Protection Degree | IP20 (with all modules, terminals and covers in place) |
Mounting Rail | 35 mm DIN rail (depth 7.5 mm or 15 mm) |
Vibration Resistance | IEC 60068-2-6: 2–8.4 Hz: 3.5 mm, 8.4–150 Hz: 1g |
Shock Resistance | IEC 60068-2-27: 15 g, 11 ms, half-sine |
Screw Tightening Torque | 1.2 Nm |
Dimensions (W×H×D) | 28 × 135 × 67.5 mm |
Weight | 0.232 kg (232 g) |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of device is TU515?
A1: TU515 is an I/O terminal unit from ABB’s S500 series using 24 V DC supply and screw terminals.
Q2: How many channels does TU515 support?
A2: It supports up to 32 channels, organized in 4 groups of 8 channels each.
Q3: What mounting orientations are supported?
A3: Both horizontal and vertical mounting are supported; for vertical mounting, the output load must be reduced by 50% per group.
Q4: What is the maximum current capacity?
A4: The maximum current per separated process voltage terminal is 10 A.
Q5: Does the module support reverse polarity protection?
A5: Yes, reverse polarity protection is included for the DC supply.
Q6: What is the protection degree of this device?
A6: IP20, provided all modules, terminals, and covers are correctly installed.
Q7: Can the device operate in humid environments?
A7: Yes, it supports up to 95% relative humidity, but condensation must be avoided.
Q8: What grounding is required?
A8: The device must be grounded through the DIN rail or wall-mounting screws for safety and EMC compliance.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.