Technical Specifications
Parameter | Description |
---|---|
Module Type | 5X00062G01 (Electronics), with Personality Module 5X00063G01 |
Analog Output Channels | 8 channels, multiplexed 4-20mA analog output |
Channel Update Rate | 24 ms per channel (14-bit resolution) |
Output Signal Range | 4 to 20 mA |
D/A Resolution | 14 bits |
Accuracy Over Temp Range | ±0.25% of span |
Output Load | 230 ohms minimum to 700 ohms maximum |
Output Compliance | 20 mA @ 21.6 VDC into 700-ohm load |
Diagnostics | Open loop feedback detection; 8 Pass/Fail bits stored in register 0xC |
Channel Isolation | None between channels; 1000 VAC/VDC field-to-logic isolation (1 min) |
Power (Main) | 24 VDC, 1.2W typical, 2.5W max |
Power (Auxiliary) | 24 VDC (-5% to +6.25%), 6W typical, 7.2W max |
Operating Temperature | 0°C to 60°C |
Humidity Range | 0% to 95% non-condensing |
Dimensions | 150 x 80 x 200 mm |
Weight | 0.31 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: Are the channels isolated from each other?
A1: No. All channels share a common +24VDC auxiliary power and ground with no isolation between channels.
Q2: What is the supported output load range?
A2: The module supports 4-20mA output into loads ranging from 230 ohms to 700 ohms.
Q3: Does this module support HART protocol communication?
A3: Yes. It uses a low-level frequency shift keyed sine wave superimposed on the 4-20mA signal for HART communication.
Q4: What are the power requirements of the module?
A4: Main power: 24VDC (max 2.5W); Auxiliary power: 24VDC (max 7.2W).
Q5: Is the module accurate across temperature variations?
A5: Yes. It maintains ±0.25% span accuracy across the operating temperature range.
Q6: How can module status be monitored?
A6: Via front panel LEDs indicating Power OK, Communication OK, External Error, and Internal Error.
Q7: Does the module offer diagnostic feedback?
A7: Yes. It features open-loop detection with 8 pass/fail bits stored in register 0xC.
Q8: Is AMS Device Manager supported for smart device integration?
A8: Yes. The module is compatible with the AMS Suite for parameter management and diagnostics.