Products Description




Company Information | |||
sales@xmjzjsgs.com | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 |
Technical Specifications
Category | Description |
---|---|
Model | Woodward 9907-252 |
Power Supply | 24 VDC, range 18–32 VDC, approximately 5 W power consumption |
Output Type | +0.5 to +4.5 VDC analog signal |
3-Phase PT Inputs | 95–130 or 190–260 VAC, 50–400 Hz; 1.6 W/phase at 240 VAC |
3-Phase CT Inputs | 3–7 Arms, burden 0.1 VA/phase |
Load Sharing Input | 0–3 VDC into 25 kΩ impedance (isochronous mode); open circuit for droop |
Sync Input | Compatible with optional Woodward SPM-A synchronizer |
Speed Trim | Manual adjustment via 10 kΩ external potentiometer |
Load Signal Output | DC signal proportional to real current, used for load gain adjustment |
Load Sharing Modes | Isochronous and droop |
Operating Temp | –40 to +70 °C |
Salt Fog Test | 5% NaCl, 35 °C, 47 hrs wet / 47 hrs dry |
Humidity Test | 95% RH, 65 °C, 5 cycles of 24 hrs each |
Vibration Test | 4 G, 5 mm, 5–2000 Hz, 3 hrs/axis |
Shock Test | 40 G, 11 ms sawtooth pulse |
Installation Category | Category III; Pollution Degree 2 |
Protection Requirement | Must be housed in IP43 enclosure for EU LVD compliance |
Mounting | Any orientation, not on engine |
Dimensions (L×W×H) | 273.6 × 214.1 × 59.2 mm |
Weight | 1.488 kg (DC model) |
Standards Compliance | EMC 89/336/EEC, EN 50081-2, EN 50082-2; UL508 Industrial Control Equipment |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of engine control systems is the 9907-252 designed for?
A1: It is designed for systems accepting +0.5 to +4.5 VDC speed setting input.
Q2: Can the module share load with non-Woodward controllers?
A2: Yes, it allows load sharing with both Woodward and non-Woodward engine controls.
Q3: What load sharing modes are supported?
A3: The module supports both isochronous and droop load sharing.
Q4: How is droop mode activated?
A4: Droop mode is activated when either the external droop switch or auxiliary breaker is open.
Q5: Is manual speed adjustment available?
A5: Yes, using an external 10 kΩ potentiometer to trim output signal.
Q6: Are there environmental requirements for installation?
A6: Yes, the unit must be housed in an IP43-rated enclosure and not mounted on the engine.
Q7: Does the unit comply with EMC and industrial safety standards?
A7: Yes, it complies with EN and UL standards, including EN 50178 and UL508.
Q8: Is the module suitable for humid or corrosive environments?
A8: Yes, it passed humidity and salt fog testing for harsh industrial conditions.
Tags