Honeywell 900A01-0002 ControlEdge HC900 Analog Output Module

Honeywell 900A01-0002 ControlEdge HC900 Analog Output Module

Views:3

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
Parameter
FAQ
Products Description
https://www.tilgames.com/wp-content/uploads/2025/06/900A01-0002-2-1.jpg
https://www.tilgames.com/wp-content/uploads/2025/06/900A01-0002-3.jpg
https://www.tilgames.com/wp-content/uploads/2025/06/900A01-0002-5.jpg
https://www.tilgames.com/wp-content/uploads/2025/06/900A01-0002-6.jpg
Company Information
E-mail sales@xmjzjsgs.com
Mobile +8613666033393
Whatsapp +8613666033393
WeChat 13666033393
Parameter

Manufacturer:Honeywell

Product Number:900A01-0002

Product Type:Analog Output Module

Origin:USA

Dimensions:137 × 35.6 × 137.16 mm

Weight:0.21 kg

FAQ

FAQ

Q1: How many analog outputs does the 900A01-0002 module support?
A1: The module provides 4 isolated analog current output channels.

Q2: What is the output current range of the module?
A2: Each output can be configured from 0 to 21.8 mA and scaled by the user as needed.

Q3: Are the output channels galvanically isolated?
A3: Yes, each output is isolated from the others (500 VDC) and from logic circuits (600 VDC).

Q4: Does the module support a failsafe value?
A4: Yes, a user-specified failsafe output value can be configured for loss of communication conditions.

Q5: Is output feedback supported?
A5: Yes, the module provides feedback to the controller indicating that current is flowing.

Q6: How is calibration managed for this module?
A6: Calibration data is stored in non-volatile memory; the module supports both redundant factory calibration and per-channel field calibration.

Q7: What is the maximum allowable load resistance per output?
A7: Each output can drive a load of up to 750 ohms.

Q8: How many of these modules can be installed in a single I/O rack?
A8: Up to 10 modules can be installed, or 12 with ambient temperature de-rating.