Technical Specifications
Parameter | Value |
---|---|
Module Type | AO561 |
Part Number | 1TNE968902R1201 |
Analog Output Channels | 2 configurable voltage or current outputs |
Output Type | Bipolar voltage, unipolar current |
Output Resolution | 12-bit incl. sign; 13-bit incl. sign (from version E0 onward) |
Output Error | Typ. ±0.5%, Max. ±2% (0°C to +60°C or under EMC conditions) |
Max Voltage Output Load | ±2 mA max |
Current Output Load Resistance | 0 Ω to 500 Ω |
Rated Power Supply Voltage | 24 V DC |
Inrush Current | Typ. 0.1 A²s; Max. 0.16 A²s |
Power Dissipation | Max. 3.1 W; 1 W (E0 version or later) |
Galvanic Isolation | No |
Overvoltage Protection | Yes, up to 30 V DC |
Max Cable Length (Shielded) | 100 m |
Mounting | Horizontal or vertical |
Cooling | Natural convection only |
EMC Compliance | According to IEC 61000 industrial standards |
Protection Class | IP20 (fully closed and connected) |
Mounting Rail | DIN rail 35 mm (IEC 60715) |
Fastening Screw | M4 screw, torque 1.2 Nm |
Vibration/Shock Resistance | Per IEC 60068-2-6 / 2-27 |
Operating Temperature | 0°C to +60°C (horizontal), 0°C to +40°C (vertical, load halved) |
Storage Temperature | -40°C to +70°C |
Dimensions | 135 x 74 x 34 mm |
Weight | 0.118 kg (approx. 120 g) |
FAQ
Frequently Asked Questions (FAQ)
Q1: How many analog outputs does the AO561 module support?
A1: The module supports 2 configurable analog output channels.
Q2: What types of output signals are available?
A2: Voltage (bipolar) and current (unipolar) output are supported.
Q3: Does the module offer overvoltage protection?
A3: Yes, it is protected against overvoltage up to 30 V DC.
Q4: What should be considered during installation?
A4: It can be mounted horizontally or vertically with unblocked convection cooling.
Q5: Is there galvanic isolation in the AO561?
A5: No, the module does not provide galvanic isolation.
Q6: What is the maximum supported load resistance for current output?
A6: Up to 500 Ω.
Q7: What kind of terminal blocks are compatible?
A7: 11-pin spring or screw terminal blocks such as TA563-11, TA564-11, TA565-11.
Q8: What is the allowable operating temperature range?
A8: 0°C to +60°C when mounted horizontally, 0°C to +40°C when mounted vertically with load derated.