Technical Specifications
Parameter Category | Value |
---|---|
Number of Output Channels | 8 transistor outputs (24 V DC, max. 0.5 A per channel) |
Channel Grouping | 1 group (8 channels per group) |
Signal Terminals | O0–O7: Terminals 11–18 |
Common Voltage Terminal | Terminal 19 (UP, +24 V DC) |
Reference Terminal | Terminal 20 (ZP, 0 V DC) |
Rated Current per Channel | 0.5 A |
Max Current per Group | 4 A |
Min Output Voltage (Signal 1) | ≥ 20 V DC |
Output Delay | 0 to 1: Max 50 µs; 1 to 0: Max 200 µs |
Output Data Length | 1 byte |
LED Indicators | 1 yellow LED per channel |
Leakage Current (Signal 0) | 0.5 mA |
Supported Loads | Inductive: max 0.5 Hz; Lamp: max 11 Hz @ 5 W |
Short Circuit/Overload Protection | No; external 3 A fast-blow fuse required |
Galvanic Isolation | Yes, between output group and module |
Max Surge Voltage | 35 V DC for 0.5 seconds |
Power Dissipation | Max. 1 W |
Cable Length | Shielded: 500 m; Unshielded: 150 m |
Mounting Orientation | Horizontal or vertical |
Cooling Method | Natural convection |
Dimensions (W x H x D) | 75 x 135 x 34 mm |
Weight | 0.118 kg (approx. 115 g) |
Protection Rating | IP20 (with all modules and covers closed) |
Mounting Method | DIN rail 35 mm or M4 screws |
FAQ
Frequently Asked Questions (FAQ)
Q1: What types of loads can the DO561 module support?
A1: It supports inductive loads (up to 0.5 Hz) and lamp loads (up to 11 Hz, max 5 W).
Q2: What is the rated output current per channel?
A2: The maximum rated output current per channel is 0.5 A.
Q3: Does the module include overload or short-circuit protection?
A3: No, external 3 A fast-blow fuses are required for each channel.
Q4: Is the module galvanically isolated?
A4: Yes, there is galvanic isolation between the output group and the rest of the module.
Q5: What mounting orientations are supported?
A5: Both horizontal and vertical mounting are supported. In vertical orientation, output loads must be reduced by 50% per group.
Q6: Does each channel have status indication?
A6: Yes, each channel is equipped with a yellow LED to indicate output status.
Q7: What is the maximum surge voltage the module can withstand?
A7: The module can withstand up to 35 V DC for 0.5 seconds.
Q8: What are the module’s physical dimensions and weight?
A8: The module measures 75 x 135 x 34 mm and weighs approximately 0.118 kg.