Technical Specifications
Parameter | Description |
---|---|
Model | TU847 |
Article Number | 3BSE022462R1 |
Communication Protocol | PROFIBUS DP-V1 |
Redundancy Support | Yes (for CI840/CI840A) |
Hot Swap | No |
Power Input | 24 V DC (range: 19.2 – 30 V) |
ModuleBus Current Distribution | 5 V: max 1.5 A, 24 V: max 1.5 A |
Rated Insulation Voltage | 50 V |
Dielectric Test Voltage | 500 V AC |
Operating Temperature | 0 to +55 °C (recommended: +5 to +55 °C) |
Storage Temperature | -40 to +70 °C |
Relative Humidity | 5% to 95%, non-condensing |
Mounting Orientation | Vertical or Horizontal |
Mechanical Key Combinations | 36 |
Wire Size | 0.25 – 2.5 mm² (24 – 14 AWG) |
Torque | 0.5 – 0.6 Nm |
Stripping Length | 6 – 7.5 mm |
Ingress Protection | IP20 (IEC 529) |
Equipment Class | Class I (IEC 60536) |
Certifications | CE, cULus Class1 Zone 2, ATEX Zone 2, Marine (ABS, DNV-GL, BV, LR) |
RoHS/WEEE Compliance | Yes (DIRECTIVE/2011/65/EU, 2012/19/EU) |
Dimensions (W x H x D) | 124 x 186 x 47 mm |
Weight | 0.5 kg |
FAQ
FAQ – Frequently Asked Questions
Q1: What is the main function of the TU847 termination unit?
A1: It serves as a termination interface for redundant CI840/CI840A modules in S800 I/O systems, handling power, communication, and mechanical keying.
Q2: Can the TU847 be hot-swapped during system operation?
A2: No, the TU847 does not support hot-swapping and should not be replaced under power.
Q3: What types of connectors does TU847 support?
A3: It features DSUB9 connectors for PROFIBUS and RJ45 ports for service tools.
Q4: How many mechanical keying combinations does TU847 offer?
A4: It provides 36 mechanical keying combinations to prevent incorrect module insertion.
Q5: Is the TU847 suitable for hazardous locations?
A5: Yes, it is certified for use in cULus Class1 Zone 2 and ATEX Zone 2 environments.
Q6: Can it be mounted in both vertical and horizontal orientations?
A6: Yes, TU847 supports both mounting orientations.
Q7: What is the maximum ambient operating temperature for vertical installation?
A7: 40 °C is the recommended maximum for vertical mounting.
Q8: What safety and environmental standards does it comply with?
A8: It complies with EN/UL 61010 safety standards, RoHS, and WEEE directives.