Technical Specifications
Parameter Category | Detailed Specification |
---|---|
Product Name | Bently Nevada 990-04-50-01-01 Vibration Transmitter |
Input | Accepts 1 non-contacting 3300 NSv Proximity Probe and extension |
Output Signal | 4–20 mA DC, 2-wire, peak-to-peak vibration |
Power Supply | +12 to +35 VDC |
Loop Resistance | Max 1000 Ω at 35 VDC |
Current Limit | 23 mA typical |
Zero/Span Adjustment | Non-interacting external potentiometers |
Frequency Response | 5 Hz to 6,000 Hz, +0, -3 dB |
Probe Gap | 0.5 to 1.75 mm (20 to 55 mils) |
Prox OUT Output Impedance | 10 kΩ for 10 MΩ load |
Temperature Stability | ±10% of 7.87 mV/μm |
Operating Temp (TX) | -35°C to +85°C |
Storage Temp (TX) | -52°C to +100°C |
Operating Temp (Probe) | -52°C to +177°C |
Storage Temp (Probe) | -52°C to +177°C |
Relative Humidity | 100% condensing, non-submerged |
Enclosure Material | AISI 303 or 304 Stainless Steel |
Probe Tip Material | Polyphenylene Sulfide (PPS) |
Mounting Options | DIN rail or bulkhead screws |
Frequency Range | 5 Hz – 6 kHz |
Product Dimensions | 100.1 x 73.9 x 53.3 mm |
Product Weight | 0.43 kg (0.9 lbm) |
Typical System Weight | 0.82 kg (including probe and cable) |
FAQ
Frequently Asked Questions (FAQ)
Q1: What types of probes are compatible with this transmitter?
A1: It is compatible with Bently Nevada 3300 NSv non-contacting proximity probes and extension cables.
Q2: Does it support standard 4-20 mA output?
A2: Yes, the 990 transmitter provides a standard 4-20 mA output proportional to peak-to-peak vibration.
Q3: Can the device be used for diagnostics?
A3: Yes, it provides dynamic signal output via “PROX OUT” for diagnostics, preferably with the 990/991 Test Adapter for isolation.
Q4: What are the mounting options available?
A4: It can be mounted using DIN rail clips or bulkhead screws.
Q5: Is the unit suitable for high-humidity environments?
A5: Yes, the potted construction supports use in up to 100% condensing humidity environments.
Q6: Does the device include fault detection?
A6: Yes, it outputs less than 3.6 mA within 100 μs upon a Not OK condition, preventing false alarms.
Q7: Is the transmitter certified for hazardous areas?
A7: Yes, it holds multiple hazardous area approvals including ATEX and Class I Div 2.
Q8: What is the accuracy of the output signal?
A8: The output signal has an accuracy of ±1.5% over the full scale, measured across a 250Ω loop.