Products Description




Company Information | |||
sales@xmjzjsgs.com | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 |
Parameter
Manufacturer:GE
Product Number:IC200ALG620-EC
Product Type:Analog Input Module
Origin:USA
Dimensions:110 x 66.8 x 50 mm
Weight:0.39 kg
FAQ
FAQ
Q1: What RTD types are supported by the IC200ALG620 module?
A1: The module supports 25, 100, and 1000 ohm platinum RTDs, 10, 50, and 100 ohm copper RTDs, 100 and 120 ohm nickel RTDs, and 604 ohm nickel/iron RTDs.
Q2: What is the operating temperature range of the IC200ALG620 module?
A2: The operating temperature range is 0°C to 60°C.
Q3: What is the accuracy of the IC200ALG620 module?
A3: The accuracy is ±0.15% for both resistance measurements and temperature measurements at 25°C.
Q4: Can I connect 3-wire and 4-wire RTDs to the module?
A4: Yes, the module supports both 3-wire and 4-wire RTDs.
Q5: What is the update rate of the IC200ALG620 module?
A5: The update rate is approximately 210 ms per channel at 60 Hz, and 230 ms per channel at 50 Hz.
Q6: What types of alarms are supported by the module?
A6: The module supports high/low alarms, under-range/over-range alarms, open wire alarms, and input short alarms.
Q7: Does the IC200ALG620 module require an external power supply?
A7: No, the module does not require an external power supply. It provides the excitation current for the RTDs internally.
Q8: What is the maximum lead resistance allowed for the RTDs?
A8: The maximum lead resistance is 50 ohms per lead.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.