Description
Parameter
FAQ
Products Description
https://www.tilgames.com/wp-content/uploads/2025/04/IC693ALG223D-4-1.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/IC693ALG223D-2.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/IC693ALG223D-3.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/IC693ALG223D.jpg
Company Information
E-mail sales@xmjzjsgs.com
Mobile +8613666033393
Whatsapp +8613666033393
WeChat 13666033393
Parameter

Manufacturer:GE Fanuc

Product Number:IC693ALG223D

Product Type:Analog Current Input Module

Origin:USA

Dimensions:51 x 127 x 127 mm

Weight:0.458 kg

FAQ

FAQs:

  • Q: What is the input current range for the IC693ALG223D module?
    A: The module supports three input ranges: 0 to 20 mA, 4 to 20 mA, and 4 to 20 mA Enhanced.

  • Q: How many channels does the IC693ALG223D module support?
    A: The module supports up to 16 channels, which are individually configurable.

  • Q: What is the resolution of the IC693ALG223D module?
    A: The resolution is 4 μA per bit for the 4 to 20 mA range and 5 μA per bit for the 0 to 20 mA and 4 to 20 mA Enhanced ranges.

  • Q: What is the update rate of the IC693ALG223D module?
    A: The update rate of the module is 6 milliseconds.

  • Q: What is the power consumption of the IC693ALG223D module?
    A: The module consumes 120 mA from the +5 VDC bus and 65 mA from the external 24 VDC supply.

  • Q: What is the maximum isolation rating for the IC693ALG223D module?
    A: The isolation is 250 VAC continuous and 1500 VAC for 1 minute.

  • Q: How do I configure the IC693ALG223D module?
    A: Configuration is done through the Proficy Machine Edition software, allowing you to set parameters such as input range, channel assignments, and alarm limits.

  • Q: Can I use the IC693ALG223D module in hazardous locations?
    A: Yes, the module is suitable for use in Class I, Division 2 hazardous locations, with proper installation and precautions.