Technical Specifications
Parameter | Specification |
---|---|
Model | 2MLQ-SS2A |
Output Points | 16 points |
Isolation Method | Photo coupler isolation |
Rated Load Voltage | AC 100–240V (50/60Hz) |
Maximum Load Voltage | AC 264V |
Maximum Load Current | 0.6A per point, 4A per COM |
Minimum Load Current | 20mA |
Off Leakage Current | 2.5mA (AC 220V, 60Hz) |
Max Inrush Current | 20A per cycle or less |
Max Voltage Drop (On) | ≤ AC 1.5V (at 2A) |
Surge Absorber | Varistor (387–473V), C.R Absorber |
Response Time (Off → On) | ≤ 1ms |
Response Time (On → Off) | ≤ 0.5 cycle + 1ms |
Common Method | 16 points / 1 COM |
Current Consumption | 300mA (when all outputs are ON) |
Operation Indicator | LED ON when output is ON |
External Connection Method | 18-point terminal block (M3 x 6 screw) |
Dimensions (W×H×D) | 114 × 48 × 127 mm |
Weight | 0.2 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of load is suitable for the 2MLQ-SS2A module?
A1: The module is designed for resistive AC loads such as lighting and small heating elements. It supports AC voltages from 100V to 240V.
Q2: What is the maximum output current per channel?
A2: Each channel can handle up to 0.6A. The combined output current for all channels tied to a single COM should not exceed 4A.
Q3: Does the module include surge protection?
A3: Yes, it is equipped with a varistor and C.R absorber that comply with IEC 61006-6-2 for effective surge suppression.
Q4: How fast does the module respond?
A4: The switching response time is very quick—1 ms or less from OFF to ON, and 0.5 cycle plus 1 ms or less from ON to OFF.
Q5: What output type does this module use?
A5: The 2MLQ-SS2A uses Triac output, which is specifically suited for controlling AC power.
Q6: Does the LED indicator remain functional if external power is lost?
A6: The LED indicators operate independently and will continue to reflect output status as long as the module is powered.
Q7: Are the output channels electrically isolated?
A7: Yes, each output channel is optically isolated using photo couplers for safety and signal integrity.
Q8: Can this module be installed in any slot within the system?
A8: Yes, the MasterLogic-200 system allows flexible installation of modules in any I/O slot without restriction.