Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 |
Technical Specifications
Parameter | Specification |
---|---|
Module Model | 8C-PDIPA1 – Digital Input Pulse Accumulation, Coated |
IOTA Model | 8C-TDILA1 (Non-Redundant, 9”) / 8C-TDILB1 (Redundant, 12”) |
Input Channels | 32 (Channels 1–16 configurable for pulse accumulation, 17–32 as digital input) |
Input Voltage Rating | 24 VDC |
DI Power Supply Range | 18 to 30 VDC |
Module Current Consumption | 105 mA |
Galvanic Isolation | 1000 VAC RMS |
Isolation Technique | Optical (in IOM) |
Signal Type (Pulse) | Accumulation: 0–1 kHz, 30% minimum duty cycle |
Minimum Pulse Width | 300 µs |
Channel Scan Time | 300 µs |
ON Sense Voltage/Current | ≥13 VDC or ≥3 mA |
OFF Sense Voltage/Current | ≤5 VDC or ≤1.2 mA |
Input Impedance | 4.2 kΩ |
Delay (Input Filter + Isolation) | 5 ms ± 20% |
Module Insertion/Removal | Supported under power |
Dimensions (W x H x D) | 60 x 155 x 145 mm |
Weight | 0.3 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What is the purpose of the 8C-PDIPA1 module?
A1: It is designed for 24VDC digital pulse accumulation and digital input signal acquisition.
Q2: How many channels support pulse accumulation?
A2: Channels 1 to 16 can be configured for pulse accumulation; channels 17 to 32 are used for digital input.
Q3: What is the supported pulse frequency range?
A3: It supports up to 1 kHz for devices with a minimum 30% duty cycle.
Q4: What isolation method is used in this module?
A4: Optical isolation is used for galvanic separation between channels and the system.
Q5: Can the module be inserted or removed while powered?
A5: Yes, hot swapping is supported.
Q6: What is the minimum pulse width detectable by the module?
A6: The minimum pulse width supported is 300 microseconds.
Q7: Does this module support redundancy?
A7: Yes, when used with the 8C-TDILB1 IOTA module.
Q8: What are the power requirements for the module?
A8: It operates with a power supply voltage of 18 to 30 VDC and consumes 105 mA.