Technical Specifications
Parameter | Description |
---|---|
Model | CP451-50 |
Type | High-performance control processor module |
System Interface | Vnet/IP, FIO |
Processor | 32-bit RISC microprocessor for high-speed processing |
Memory Capacity | Program: up to 2 MB; Data: up to 1 MB |
Real-Time Clock | Built-in, supports time synchronization |
Redundancy | Supports CPU redundancy |
Communication Ports | 1 Ethernet port for Vnet/IP |
Compatible Units | Can be installed in AFV30, AFV40, AFV10 Field Control Units |
Mounting | 19-inch rack mount |
Power Supply | Supplied by FCU |
Operating Temperature | 0 to 50°C |
Storage Temperature | -20 to 60°C (avoid direct sunlight) |
Humidity | 5 to 95% RH, non-condensing |
Vibration Resistance | Continuous: ≤2.0 m/s² (14–100Hz); Shock: ≤98.0 m/s² (vertical) |
EMC Immunity | Electric field ≤ 3 V/m (26 MHz to 2.7 GHz) |
Altitude | ≤ 2000 meters |
Dimensions | 66 x 49 x 125 mm |
Weight | 0.45 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What system architectures does the CP451-50 support?
A1: It supports Vnet/IP and FIO (Fieldnetwork I/O) systems, ideal for CENTUM VP DCS.
Q2: Does the CP451-50 support redundancy?
A2: Yes, it supports CPU redundancy for increased reliability.
Q3: Which FCUs are compatible with the CP451-50?
A3: The CP451-50 is compatible with AFV30, AFV40, and AFV10 series Field Control Units.
Q4: What communication protocols are supported?
A4: It supports Vnet/IP via an integrated Ethernet port.
Q5: Are there any installation restrictions?
A5: It must be installed in a Yokogawa-standard rack with proper power and within rated environmental conditions.
Q6: Does the module include a real-time clock?
A6: Yes, it has a built-in RTC with synchronization capability.
Q7: What are the typical applications for this module?
A7: Commonly used in process industries like chemical, oil & gas, and power generation in DCS architectures.
Q8: Is the CP451-50 compliant with EMC and safety standards?
A8: Yes, it complies with CE, CSA, and other relevant industrial standards and EMC immunity requirements.