Yokogawa SDV521-S33 Digital Output Module

Yokogawa SDV521-S33 Digital Output Module

Manufacturer:Yokogawa

Product Number:SDV521-S33

Product Type:Digital Output Module

Origin:Japan

Dimensions:130 x 32.8 x 125.5 mm

Weight:0.36 kg

Views:3

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
https://www.tilgames.com/wp-content/uploads/2025/05/SDV521-S33-1-1.jpg
https://www.tilgames.com/wp-content/uploads/2025/05/SDV521-S33-2.jpg
https://www.tilgames.com/wp-content/uploads/2025/05/SDV521-S33-3.jpg
https://www.tilgames.com/wp-content/uploads/2025/05/SDV521-S33-4.jpg
Company Information
E-mail [email protected]
Mobile +8613666033393
Whatsapp +8613666033393
WeChat 13666033393

Technical Specifications

Parameter Details
Model SDV521-S33
Number of Outputs 4 channels, module isolation
Output Voltage 24 V DC
Output Voltage Drop Max 1 V
External Power Supply 24 V DC, minimum 10 A
Voltage Tolerance 24 V DC +20% / -10%
Current Capacity 8.2 A
Max Leakage Current (OFF) 1.6 mA
Output Format Current source
Max Load Current/Channel 2 A
Total Output Max Current 8 A (total across all 4 channels)
Min Load Current 100 mA
Load Resistance Range 12 to 240 Ω
Max Lamp Load 1 A per channel (supports up to 10x inrush)
Output Response Time Max 30 ms
Withstand Voltage 2 kV AC between output and system (1 min)
Power Consumption (5V) Max 280 mA
Power Consumption (24V) Max 140 mA
Dimensions (W x H x D) 130 x 32.8 x 125.5 mm
Weight 0.36 kg
External Connection Dedicated signal cable (AKB651)
FAQ

Frequently Asked Questions (FAQ)

Q1: What is the output voltage of the SDV521-S33 module?
A1: The output voltage is 24 V DC, suitable for field equipment control.

Q2: What is the maximum load current per output channel?
A2: Each channel can handle up to 2 A, with a total of 8 A across all channels.

Q3: What is the minimum load current requirement?
A3: The minimum load current per channel is 100 mA.

Q4: Does the module offer isolation?
A4: Yes, the SDV521-S33 provides module-level isolation for electrical safety.

Q5: What is the allowable load resistance range?
A5: The load resistance must be within 12 to 240 ohms.

Q6: Can it drive lamp-type loads?
A6: Yes, it supports up to 1 A per channel for lamps, and can tolerate up to 10 times inrush current.

Q7: What are the dimensions and weight of the module?
A7: The module measures 130 x 32.8 x 125.5 mm and weighs approximately 0.36 kg.

Q8: What type of cable is required for external connection?
A8: It requires the dedicated signal cable model AKB651.